7845GSM/7845GSMCN Installation and Setup Guide
1-2
The control treats the module as a Long Range Radio (LRR) device, so program the control
accordingly, including setting the module’s proper LRR device address
Reports are sent in Contact ID format
The module also supports two hardwire zone trigger inputs (zones 6 and 7)
Zone Trigger Mode
This mode is for use with controls that do not support LRR-ECP communication nor 4204
Relay Modules
The module provides six input zones
Each zone can be configured for +V, -V, or EOLR triggering
Each zone can be programmed for inverted operation, delayed reporting, and restoral
reporting
Zone 1 input can distinguish between pulsed and steady signals and report fire or
burglary alarms respectively
Zone 1 can also be programmed to report Lynx panic (if used with Lynx control)
Reports are sent in ADEMCO High-Speed format
4204 Mode and Two-4204 Mode
This mode is for use with Honeywell controls that do not support LRR-ECP
communication, but that do support 4204 Relay Modules
The module connects to the control’s keypad terminals
The control treats the module as 4204 Relay Module(s), so program the control
accordingly, including setting the module’s proper 4204 device address
4204 mode provides up to four zone inputs, plus two optional trigger zones, depending on
options programmed
Two-4204 mode provides up to eight zone inputs, depending on options programmed
Each 4204 zone can be programmed for delayed reporting and restoral reporting
Reports are sent in ADEMCO High-Speed format
Module Supervision Features
The 7845GSM provides the following types of supervision and module fault detection:
Network communication failure
: In the event the AlarmNet network does not hear a
supervisory message from the module within a specified time (“Supervision” option, 24
hours, 30 days, or none), AlarmNet notifies the central station of a communication failure.
Communication path failure
: In the event the module detects a communication path
failure, the control panel can be notified of a trouble condition with the module after a
specified time has elapsed (“GSM Flt Time” option, 00-99 minutes).
Fault output
: Terminal 11 can serve as a fail-safe trigger for module fault conditions.
If used, the fault relay will trip when the following conditions occur: tamper*, power loss*,
low battery*, battery charger fault*, loss of network connectivity*, the device is not
registered and the device is remotely disabled by AlarmNet.
*Alarm reporting for the noted condition must be enabled for it to trigger the fault relay.
Primary power loss and low battery conditions (“Pwr Loss Rpt,” “Low Bat Rpt” options).
Cover tamper condition (“Tamper Rpt” option).