AlarmNet 7845C Manuale Utente

Navigare online o scaricare Manuale Utente per Sistemi di controllo di accesso AlarmNet 7845C. •Subscriber Messages - AZ Security Control Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa

Sommario

Pagina 2 - Page 2

The status channel (9th channel) identifies the type of message0 = Diagnostic Messages1 = Notification Message2 = Not applicable to radio accounts3 =

Pagina 3 - Please note:

Status Channel = 0 (Diagnostic Message)Message Definition: Applies to:Key Indicator: “D” in 3rd channelcccc 00D0 010C 0 Authorized radio substitution

Pagina 4 - Message Formats

t = Pass/Fail result: A = Acceptable F = FailureKey Indicator: “6” in 4th channelcccc nng6 ssfm 0F-type diagnostic (dialer)nn = number of the node

Pagina 5 - Ademco Contact ID format:

0012 = 2-Way radio internal tamper0013 = Authentication – no response0014 = Authentication Violation0015 = Authentication Initialized* Messages for ac

Pagina 6 - Reading a Contact ID message

Status Channel = 1 (Notification Message)Message Definition: Applies to:0000 5555 5555 1Network Alert Message – Tells the C/S to refer to their e-mail

Pagina 7 - Page 7

Status Channel = 5 (Subscriber Trouble / Special Report)Message Definition: Applies to:Key Indicator: Account # = “0000” or “0001”0000 5555 5515 5000

Pagina 8 - Ademco High-Speed format:

Status Channel = 6 (Status Message)Note: Each channel of these message types corresponds to a particular type of event. Because there are eight chan

Pagina 9 - Reading a High Speed message

Status Channel = 7 (Alarm condition)Notes: Each channel of these message types corresponds to a particular type of event. Because there are eight ch

Pagina 10

a fire alarm control, supervisory faults from the fire control panel may be used to trigger one or more of the eight channels on the 7620UL

Pagina 11 - AlarmNet Messages Page 11

Status Channel = 8 (Alarm with low battery (older 7620 radio only))Notes: Each channel of these message types corresponds to a particular type of eve

Pagina 12 - AlarmNet Messages Page 12

Definitions of AlarmNet Network and Subscriber MessagesAlarmNet Messages Page 2

Pagina 13 - AlarmNet Messages Page 13

Status Channel = 9 (Installer generated test message)Message Definition: Applies to:cccc 5555 5555 9System Test Message Manually triggered test from

Pagina 14 - AlarmNet Messages Page 14

GlossaryItem Description2-Way radio internal tamperThis feature is currently not available.AC Loss Indicates that the radio has detected a

Pagina 15 - AlarmNet Messages Page 15

After 60 days of being unsupervised, the interval between successive A-Type Diagnostics will increase to 24 hours. (Please note that after 60 days

Pagina 16 - AlarmNet Messages Page 16

Communications Failure RestoreA Communications Failure will restore when the network again hears from the radio in question. Comm Fail Restorals are s

Pagina 17 - AlarmNet Messages Page 17

Fire trouble see “Fire Supervisory Fault”Frequency Error This feature is currently not available.F-Type DiagnosticsBoth One-Way and Two-Way A

Pagina 18 - AlarmNet Messages Page 18

send this message. This may occur if the keypad wiring is cut or shorted, or if the control is no longer functioning. A “Check” message may also dis

Pagina 19 - AlarmNet Messages Page 19

Modulation Error This feature is currently not available.Multiple nodes downThis message is similar to the “Redundant supervision warning” except that

Pagina 20 - AlarmNet Messages Page 20

the signal strengths involved. If 30 or more transmissions are heard within the specific time period, they will then be evaluated based on the avera

Pagina 21 - Glossary

purpose of maintaining a secure radio connection while the alarm system is violated, the power-up reset message will be sent to the central station fr

Pagina 22 - Page 22

System Supervisory FaultThis message indicates that the 7720ULF has either detected a problem with “Bell Supervision”, or has detected a “Ground Fault

Pagina 23 - Page 23

Please note: The information contained in this document assumes the user has knowledge of central station receivers, formats, procedures, and program

Pagina 24 - Page 24

AlarmNet MessagesVersion Dated AlarmNet Messages Page 30

Pagina 25

Message FormatsThere are two types of messages that are sent by AlarmNet:1 – Subscriber Messages – indicate alarm or trouble conditions at the subscri

Pagina 26

Ademco Contact ID format: Transmitted in DTMF (touch-tone)  Consists of o A four digit subscriber ID o A ‘qualifier’ that indicates whether the mess

Pagina 27 - Page 27

How Contact ID is displayed on the printerReading a Contact ID message1 – The “Event Qualifier” is a single character that can be: “E” for an Event O

Pagina 28 - Page 28

4 – The last three digits are the “Zone or User” number, which specifies the exact zone number that caused the event, or the user number transmitting

Pagina 29 - Page 29

Ademco High-Speed format:  Is transmitted in DTMF (touch-tone)  Consists of o A four digit subscriber ID o Eight channels of information indicating

Pagina 30 - Version Dated

How High Speed is displayed on the 685 receiverHow High Speed is displayed on the printerReading a High Speed messageTo decode a High Speed message, f

Commenti su questo manuale